Powerware 9355 |
Rating |
8kVA |
10kVA |
12kVA |
15kVA |
20kVA |
30kVA |
Part number |
9355-8-N |
9355-10-N |
9355-12-N |
9355-15-N |
9355-20-N |
9355-30-N |
Capacity (VA/watts) |
8 / 7.2 |
10 / 9 |
12 / 10.8 |
15 / 13.5 |
20 / 18 |
30 / 27 |
Dimensions HxWxD (mm)
UPS + BAT
UPS + 2*BAT |
817x305x702
1214x305x702
|
817x305x702
1214x305x702
|
817x305x702
1214x305x702
|
817x305x702
1214x305x702
|
1684x484x762
|
1684x484x762
|
Weight (kg)
UPS + BAT
UPS + 2*BAT |
155 kg
265 kg
|
155 kg
265 kg
|
160 kg
270 kg
|
160 kg
270 kg
|
200 kg
300-500 kg
|
300 kg
400-500 kg
|
Input connection |
Hardwired |
Output connection |
Hardwired |
Typical runtime at +25 oC. |
UPS + BAT |
15 min |
10 min |
8 min |
5 min |
5 min |
- min |
UPS + 2BAT |
33 min |
25 min |
20 min |
15 min |
13 min |
7 min |
Operational |
Nominal input voltage (Vac) |
220/380, 230/400, 240/415 Vac three phase |
Input voltage range |
+20%, -20% |
Operating frequency |
50/60 Hz (45 to 65 Hz) |
Input power factor |
0.99 |
Input current distortion |
5% THD |
Nominal output voltage |
220/380, 230/400, 240/415 Vac three phase |
Output voltage regulation |
±2% static;
±5% dynamic at 100% load change, <1 ms response time |
Overload capacity |
150% for 5 sec / 125% for 1 min (online),
1000% for 5 msec (bypass) |
Efficiency |
92% with rated non-linear load |
User interface |
LCD-display |
Std. Graphical LDC with blue back light |
LED |
4 LED |
Standard communication ports |
1 x RS232 for local support, 2 x X-slot (empty);
1 x relay contacts, 2 x input contacts, 1 x emergency power off input |
Optional |
External battery cabinets;
Isolation transformer;
X-slot: SNMP/web, Modbus/Jbus, Relay card; |
Environmental |
Operating Temperature |
0oC to +40 oC |
Storage Temp |
-15°C to +40°C |
Altitude |
< 1000 M |
Audible Noise at 1 meter; |
<50 dB |
Certification |
Quality |
ISO 9001 |
Markings |
CE-marking |
Safety |
IEC 62040-1-1, IEC 60950 |
EMC |
EN 50091-2 Class A |